MBus to Modbus Series Building & Industrial IoT Gateway

These DIN‑rail mounted Linux‑powered gateways collect data from M‑Bus meters, deliver M‑Bus to Modbus RTU/TCP protocol conversion with dynamic point capacity ranging 256‑512 points, support HTML5 web configuration, connect MBus measuring devices to mainstream building automation and industrial SCADA configuration systems.

Selection and Comparison

MBus‑to‑Modbus Gateway Hardware Parameter
Hardware Parameter Comparison Table
Parameter MOD1001‑MBus MOD1002‑MBus MOD1010‑MBus MOD1011‑MBus
Supported Tags 256 512 256 512
Ethernet Port 1 × 10/100M Ethernet Port
MBus Port ‑ ‑ 1 × MBus Port(COM1) 1 × MBus Port(COM1)
RS485 Port(Isolated) 1 × COM1 2 × COM1,COM2 ‑ 1 × COM2
Collection Protocol MBus_Water Meter(CJ188)
MBus_Energy Meter(CJ188)
MBus_Energy Meter_EN
ModbusRTU Client
ModbusTCP Client
DLT 645‑1997
DLT 645‑2007
MBus_Water Meter(CJ188)
MBus_Energy Meter(CJ188)
MBus_Energy Meter_EN
ModbusRTU Client
ModbusTCP Client
DLT 645‑1997
DLT 645‑2007
MBus_Water Meter(CJ188)
MBus_Energy Meter(CJ188)
MBus_Energy Meter_EN
ModbusTCP Client
MBus_Water Meter(CJ188)
MBus_Energy Meter(CJ188)
MBus_Energy Meter_EN
ModbusRTU Client
ModbusTCP Client
DLT 645‑1997
DLT 645‑2007
Transfer Protocol Modbus RTU / Modbus TCP Modbus RTU / Modbus TCP Modbus TCP Modbus RTU / Modbus TCP
Dimensions(L×W×H) 119mm × 55mm × 33mm 119mm × 55mm × 33mm 119mm × 55mm × 33mm 117.6mm × 54.5mm × 32.7mm
MBus Static Voltage ‑ ‑ 30V‑36V DC 30V‑36V DC
MBus Send Voltage ‑ ‑ 20V‑24V DC 20V‑24V DC
Common Core Parameters (All Models)
Parameter Value
CPU 1‑Core 750MHz
RAM 64M
Power Consumption 6W
Power Supply AC/DC 12‑24V(2‑wire MBus meters require 24V power supply)
Weight 210g
Material Galvanized Steel
Mounting DIN‑Rail / Wall‑mounted
Operating Temperature -20℃ ~ +70℃
Storage Temperature -40℃ ~ +85℃
Operating Humidity 20%‑90% non‑condensing
Storage Humidity 15%‑95% non‑condensing

Application scenarios

Integrates M‑Bus meters including water meter, energy meter, heat meter, together with Modbus RTU field devices. Realizes integration with building automation configuration software and industrial SCADA software: WinCC, Citect, IFIX, RSVIEW, KingView, ForceControl. Suitable for energy‑consumption monitoring of buildings, campuses, factories, hospitals, hotels and stadiums.